Only few typical products of this series are shown in the following pages. EHC is capable of making other customized design and manufacturing per user request.
Specifications and Parameters:
Technical parameters | index | Remark |
Rated primary current I b | 100A | |
Maximum primary current I max | 500A | |
Change ratio | 500A/400mV, 500A/30mV, 2000A/400mV | |
Rated frequency | 50Hz/60Hz | |
Fixed position accuracy level 1 2 | 0.5S class | |
Linearity | 0.10% | |
Temperature drift | ≤0.5% | |
DC bias | ≤0.1mV | The noise floor is ≤0.1mV, which means that the fixed DC component of the Roche coil itself should be less than 0.1mV to reduce environmental impact. |
Bandwidth (-3dB) | 45Hz ~ 5kHz | |
Output internal resistance | 40Ω~200Ω | |
Loading capability | 5kΩ | |
Maximum voltage | 600V | |
AC withstand voltage | 3kVAC 50Hz 1min | |
Operating temperature range | -40℃~70℃ | |
Relative humidity | ≤80%RH | |
altitude | 4000m and below | |
Flame retardant grade of housing | UL94 V-0 | |
Note: | ||
1. When installed at fixed position, the accuracy level is 0.5S | ||
2. When installed in a non-fixed position, the error deviation of the current line passing through the coil perpendicularly is ≤1%, and the error deviation of the inclined passes through the coil is ≤1.5%. | ||
Integrator: Temperature drift should be ≤0.5% under an environment of -40℃~70℃ | ||
Coil body: thermoplastic elastomer Compliant with UL 94 V-0 | ||
The Roche coil should be able to meet the requirements of 48h salt spray test, 144h humidity and heat test, combustion test, impact test and vibration test; the shell must not deform under long-term light, the surface will not crack, and the deformation and fade, and meet the requirements of 72h light test and -40℃~70℃ high and low temperature test. |